The equivalence of weighted IMF partial discharge signals pulse injection by different coupling modes in GIS

Pulse injection to simulate partial discharge (PD) is the main method for functional verification of gas insulated switchgear (GIS) ultra high frequency (UHF) PD monitoring device. Due to the different coupling modes of pulse injection in field verification, the equivalence law between simulated PD...

Full description

Saved in:
Bibliographic Details
Published in:电力工程技术 Vol. 43; no. 4; pp. 95 - 103
Main Authors: DONG Bingbing, LI Kang, GAO Changsheng, LIU Guanke, DAI Xiliang, XIA Yunfeng
Format: Journal Article
Language:Chinese
Published: Editorial Department of Electric Power Engineering Technology 01-07-2024
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Pulse injection to simulate partial discharge (PD) is the main method for functional verification of gas insulated switchgear (GIS) ultra high frequency (UHF) PD monitoring device. Due to the different coupling modes of pulse injection in field verification, the equivalence law between simulated PD and actual PD is not clear, and the effectiveness of functional verification of monitoring device cannot be guaranteed. In this paper, a typical PD defect (tip, suspension, insulator bubble) and internal/external pulse injection UHF PD detection platform for 126 kV GIS are established, and the effective pulses of UHF signals are normalized and extracted. Then a signal processing method of weighted intrinsic mode functions (IMF) based on empirical mode decomposition is proposed. The signal equivalence is characterized by calculating the average and maximum values of the Euclidean distance of the signal, and finally compared with the conventional signal deviation method. The research shows that compared with the conv
ISSN:2096-3203
DOI:10.12158/j.2096-3203.2024.04.010