Residual current detection method based on improved VMD-BPNN

To further enhance the residual current detection capability of low-voltage distribution networks, an improved adaptive residual current detection method that combines variational modal decomposition (VMD) and BP neural network (BPNN) is proposed. Firstly, the method employs the envelope entropy as...

Full description

Saved in:
Bibliographic Details
Published in:PloS one Vol. 19; no. 2; p. e0289129
Main Authors: Bai, Yunpeng, Zhang, Xiangke, Wang, Yajing, Wang, Lei, Wei, Qinqin, Zhao, Wenlei
Format: Journal Article
Language:English
Published: United States Public Library of Science 08-02-2024
Public Library of Science (PLoS)
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:To further enhance the residual current detection capability of low-voltage distribution networks, an improved adaptive residual current detection method that combines variational modal decomposition (VMD) and BP neural network (BPNN) is proposed. Firstly, the method employs the envelope entropy as the adaptability function, optimizes the [k, ɑ] combination value of the VMD decomposition using the bacterial foraging-particle swarm algorithm (BFO-PSO), and utilizes the interrelation number R as the classification index with the Least Mean Square Algorithm (LMS) to classify, filter, and extract the effective signal from the decomposed signal. Then, the extracted signals are detected by BPNN, and the training data are utilized to predict the residual current signals. Simulation and experimental data demonstrate that the proposed algorithm exhibits strong robustness and high detection accuracy. With an ambient noise of 10dB, the signal-to-noise ratio is 16.3108dB, the RMSE is 0.4359, and the goodness-of-fit is 0.9627 after processing by the algorithm presented in this paper, which are superior to the Variational Modal Decomposition-Long Short-Term Memory (VMD-LSTM) and Normalized-Least Mean Square (N-LMS) detection methods. The results were also statistically analyzed in conjunction with the Kolmogorov-Smirnov test, which demonstrated significance at the experimental data level, indicating the high accuracy of the algorithms presented in this paper and providing a certain reference for new residual current protection devices for biological body electrocution.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 23
Competing Interests: The authors have declared that no competing interests exist.
ISSN:1932-6203
1932-6203
DOI:10.1371/journal.pone.0289129