Public toilets with insufficient ventilation present high cross infection risk

Due to insufficient ventilation, public toilets present high risks for cross-infection. The study investigated 61 public toilets to identify the causes and locations of biological contaminated sources. Airborne and surface bacterial contamination, carbon dioxide concentration, and surface ammonia le...

Full description

Saved in:
Bibliographic Details
Published in:Scientific reports Vol. 11; no. 1; p. 20623
Main Authors: Lee, M. C. Jeffrey, Tham, K. W.
Format: Journal Article
Language:English
Published: London Nature Publishing Group UK 18-10-2021
Nature Publishing Group
Nature Portfolio
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Due to insufficient ventilation, public toilets present high risks for cross-infection. The study investigated 61 public toilets to identify the causes and locations of biological contaminated sources. Airborne and surface bacterial contamination, carbon dioxide concentration, and surface ammonia levels were measured. Both bacterial contamination and CO 2 are higher in non-ventilated toilets compared to their ventilated counterparts. Bacteria colony forming units (CFUs) in a public toilet with poor ventilation can reach 5 times the number of CFUs outside of the toilet. This suggests that non-ventilated public toilets present a higher risk of cross-infection. Areas near all kinds of sanitary equipment (toilet bowls, squat toilets and urinals) were highly contaminated, indicating that enhanced cleaning regimes are necessary. Further, lidless trash bins present a higher risk as contaminated matter within the trash bins is not inhibited from being released into the environment. Ventilation and cleaning need to be improved to mitigate the risk of cross-infection in public toilets.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 23
ISSN:2045-2322
2045-2322