Prospects for Boiling of Subcooled Dielectric Liquids for Supercomputer Cooling
It is shown experimentally that using forced-convection boiling of dielectric coolants of the Novec 649 Refrigerant subcooled relative to the saturation temperature makes possible removing heat flow rates up to 100 W/cm 2 from modern supercomputer chip interface. This fact creates prerequisites for...
Saved in:
Published in: | Doklady. a journal of the Russian Academy of Sciences. Physics Vol. 63; no. 2; pp. 58 - 60 |
---|---|
Main Authors: | , , , , , |
Format: | Journal Article |
Language: | English |
Published: |
Moscow
Pleiades Publishing
01-02-2018
Springer Nature B.V |
Subjects: | |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | It is shown experimentally that using forced-convection boiling of dielectric coolants of the Novec 649 Refrigerant subcooled relative to the saturation temperature makes possible removing heat flow rates up to 100 W/cm
2
from modern supercomputer chip interface. This fact creates prerequisites for the application of dielectric liquids in cooling systems of modern supercomputers with increased requirements for their operating reliability. |
---|---|