Optimization of Lead Insulations for HVDC Converter Transformers
This paper explains design considerations for lead and lead-exit insulations of HVDC converter transformer for the purpose of automated design optimization. A HVDC converter transformer should at least deal with AC, DC, and DC polarity reversal stresses, which complicate designing process of insulat...
Saved in:
Published in: | Journal of electrical engineering & technology Vol. 14; no. 5; pp. 2057 - 2063 |
---|---|
Main Authors: | , , , , |
Format: | Journal Article |
Language: | English |
Published: |
Singapore
Springer Singapore
01-09-2019
대한전기학회 |
Subjects: | |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This paper explains design considerations for lead and lead-exit insulations of HVDC converter transformer for the purpose of automated design optimization. A HVDC converter transformer should at least deal with AC, DC, and DC polarity reversal stresses, which complicate designing process of insulation structures. Design considerations for those insulations are the types of electrical stresses and design parameters of insulation shapes. The design objective of the optimization is to ensure insulation robustness with reduced size of insulation structures. Optimization results showed 16.72% and 29.07% of length reduction with sufficient robustness, for lead and lead-exit insulations, respectively. |
---|---|
ISSN: | 1975-0102 2093-7423 |
DOI: | 10.1007/s42835-019-00195-w |