Optimised dynamic control philosophy for improved performance of mine cooling systems

•An integrated control strategy for improved mine cooling performance was employed.•An ambient DB temperature prediction model was developed, tested and implemented.•A dynamic temperature set point algorithm for chillers was formulated.•The dynamic control approach was validated on a South African m...

Full description

Saved in:
Bibliographic Details
Published in:Applied thermal engineering Vol. 150; pp. 50 - 60
Main Authors: Crawford, J.A., Joubert, H.P.R., Mathews, M.J., Kleingeld, M.
Format: Journal Article
Language:English
Published: Oxford Elsevier Ltd 05-03-2019
Elsevier BV
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:•An integrated control strategy for improved mine cooling performance was employed.•An ambient DB temperature prediction model was developed, tested and implemented.•A dynamic temperature set point algorithm for chillers was formulated.•The dynamic control approach was validated on a South African mine cooling system.•Improved chiller COP was attained with no capital expenditure. Mine workers require substantial cooling and ventilation to work in a safe and habitable environment. Deep level mine cooling systems were identified as significant energy-intensive consumers to supply such cooling. Mine cooling systems can make up to 25% of a mine’s total electricity consumption. Coupled with increasing electricity costs, deep level gold mines are struggling to remain competitive. Literature reveals a need for a simple and practical solution to optimise deep level mine cooling systems for improved system performance. In this paper, an optimised dynamic control strategy is presented to optimise the control of mine cooling systems. An integrated dynamic temperature set point algorithm and ambient dry-bulb (DB) temperature prediction model was formulated, implemented and verified. The optimised dynamic control model, when compared to existing control practises, attained a chiller coefficient of performance (COP) improvement and compressor power reduction of 7% and 4% respectively. Implementation results also showed a power demand reduction of 45.7% during the evening high electricity cost period. This strategy demonstrated to be simple and cost effective while showing significant performance improvements for South African mines.
ISSN:1359-4311
1873-5606
DOI:10.1016/j.applthermaleng.2018.12.160