Radon equilibrium factor and perceived air quality in an air-conditioned auditorium in Lublin, Poland

The study reports measurements of radon and its decay products and of perceived air quality carried out in an occupied and unoccupied auditorium at the Lublin University of Technology in Lublin, Poland during three air conditioning system operation modes – air conditioning off, air conditioning on a...

Full description

Saved in:
Bibliographic Details
Published in:Indoor + built environment Vol. 27; no. 2; pp. 270 - 277
Main Authors: Polednik, Bernard, Kozak, Krzysztof, Mazur, Jadwiga, Dudzińska, Marzenna, Grządziel, Dominik, Polednik, Aleksandra
Format: Journal Article
Language:English
Published: London, England SAGE Publications 01-02-2018
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The study reports measurements of radon and its decay products and of perceived air quality carried out in an occupied and unoccupied auditorium at the Lublin University of Technology in Lublin, Poland during three air conditioning system operation modes – air conditioning off, air conditioning on and air conditioning on/off. In the air conditioning on/off mode radon and its decay product concentrations and values of perceived air quality were inversely related. During that air conditioning operation mode, the value of the mean equilibrium factor F for the unattached fraction (0.31 ± 0.19) was somewhat higher than for the attached fraction (0.24 ± 0.19) and significant negative correlations were found between F values for attached, unattached and for the sum of both progeny fractions and perceived air quality values. These findings may be of importance as they indicate that in certain air conditioning operation modes indoor air quality deteriorates along with a reduction in the radon health hazard. This, in turn may adversely affect the comfort and productivity of the room users.
ISSN:1420-326X
1423-0070
DOI:10.1177/1420326X16672277