A Data-Aided Power Transformer Differential Protection Without Inrush Blocking Module

When a slightly faulty transformer closes without load, the current waveform presents the coexistence of inrush and fault current. At this time, the inrush blocking module will block the relay, which may delay the removal of the slight fault and lead to more serious faults. To address this problem,...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery Vol. 38; no. 3; pp. 2000 - 2010
Main Authors: Lin, Zexuan, Yang, Songhao, Zhang, Yubo, Hao, Zhiguo, Zhang, Baohui
Format: Journal Article
Language:English
Published: New York IEEE 01-06-2023
The Institute of Electrical and Electronics Engineers, Inc. (IEEE)
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:When a slightly faulty transformer closes without load, the current waveform presents the coexistence of inrush and fault current. At this time, the inrush blocking module will block the relay, which may delay the removal of the slight fault and lead to more serious faults. To address this problem, this paper proposes a data-aided power transformer differential protection without inrush blocking module. The key to eliminating the negative influence of inrush current is to extract the fundamental component from the non-inrush part of the current waveform, which corresponds to the unsaturation period of the transformer core. Firstly, a data-aided module, namely an Attention module embedded Fully Convolutional Network (A-FCN), is built to distinguish the inrush and non-inrush parts of the current waveform. Then, a physical model of the current waveform is built for the non-inrush part, and the fundamental component is extracted by the nonlinear least square (NLS) algorithm. The proposed method can avoid the block of differential protections when inrush current occurs, which improves the sensitivity and rapidity of the relay, especially in the case of a weak internal fault hidden in inrush current. Finally, simulation and experimental data verify the effectiveness and generalization of the proposed method.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2022.3230468